Oil/Gas Smoke Tube Package : Oil Fired Steam Boiler

Capacity : 500 kg/hr to 15,000 kg/hr
Fuel : L.D.O., F.O., H.S.D., Natural Gas or any special liquid or gas

Manufacturing under Internationally accepted Inspection Agencies i.e. IBR, Lloyd’s, SGS, Bureau Veritas, TUV, or any others as per client’s demand

 

Model Unit AB-10 AB-15 AB-20 AB-30 AB-40 AB-50 AB-60 AB-70 AB-80 AB-90 AB-100
Evaporation F & A 100 o C
Kgs/Hr
1000 1500 2000 3000 4000 5000 6000 7000 8000 9000 10000
Rating
M2
33 48 65 95 125 155 190 220 250 280 312
Working Press
Kgs/cm2

10.54 Kgs/cm2 to 21.09 Kgs/cm2

Eff. On NCV
%

92 ± 2

FuelConsum. LDO
Kgs/Hr
60 90 120 180 240 300 360 420 480 540 600
FO Kgs/Hr 63 94.5 126 189 252 315 378 441 504 567 630
Design code

IBR-1950 or ISO/R-831

Electric Supply

415 Volts, 50Hz, 3p. 4 Wire

Feed pump
KW
3.75
3.75
5.00
5.00
5.00
7.50
10.5
10.5
10.5
10.5
10.5
Blower motor
KW
2.25
3.75
3.75
5.00
7.50
10.50
10.50
15.0
18.75
18.75
18.75
Fuel preheater
KW
6.0
9.0
9.0
12.0
15.0
18.0
18.0
18.0
18.0
18.0
18.0
Fuel pump
KW
0.50
0.75
0.75
0.75
0.75
0.75
1.5
1.5
1.5
1.5
1.5
  • Higher capacity Boilers are available on request.
  • LDO Gross Calorific Value – 10079 Kcal/Kg.
  • FO Gross Calorific Value – 9600 Kcal/Kg.